Rear Vent Configuration With Horizontal Termination (With Vertical Rise) - Lopi 864 TRV 31K CleanFace Manual

Table of Contents

Advertisement

Finalizing the Installation

Rear Vent Configuration with Horizontal Termination (with vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
22' max (6.7 m)
20 feet (6 m)
15 feet (4.5 m)
10 feet (3 m)
5 feet (1.5 m)
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
(for qualified installers only)
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 1 (stock)
Intake Restrictor # 1 (stock)
Diffuser Position # 1 (stock)
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
6/27/2019 - 1500
22' max (6.7 m)
20 feet (6 m)
15 feet (4.5 m)
10 feet (3 m)
5 feet (1.5 m)
0 feet
This is considered a
vertical elbow
29
864 31K CF Aust