Setting parameters via DIP switches

Diagnosis (S5.1...S5.3)
The DIP switches S5.1 to S5.3 are used to:
D enable diagnosis
D set the method of transfer for the diagnostic information
The DIP switches S5.4 to S5.8 are used to set:
D the CAN operating modes
S5
MODE
MODE
.
Shipped state: S5.8 to S5.1 = 00000000
DIP
Status
switch
S5.1
OFF
ON
S5.2
OFF
ON
S5.3
OFF
ON
Meaning
Diagnosis message "Overload/short circuit of a sensor
"
supply US1–US4
disabled
Diagnosis message "Overload/short circuit of a sen-
"
sor supply US1–US4
enabled
Diagnosis message "Overload/short circuit outputs
disabled
Diagnosis message "Overload/short circuit outputs
enabled
I/O data, without embedded device diagnosis informa-
tion
The byte of device diagnosis is mapped in the PDO
behind the I/O data.
"
"
1070 072 302-101 (01.06) GB