1070 072 302-101 (01.06) GB
Technical data
Radio interference suppression
D Housing (radiated variables),
test conditions
D Frequency 30 to 230 MHz
D Frequency 230 to 1000 MHz
D Mains AC current connection
D Frequency 0.15 to 0.5 MHz
D Frequency 0.5 to 30 MHz
Conducted interference interaction
D Resolution
D Voltage drop for DC
D Output voltage in the case of in-
terruption
D Repeat rate
Burst interference interaction
D Transient overvoltage
1 MHz interaction
D dampened sinus 1 MHz
symmetrical
Interaction of high-frequency volt-
ages
D on supply lines (interaction net-
work)
D on input/output lines
D shielded cables (coupling pliers)
Interaction of non-conducted
interference
IO-BOX32
Requirement from EN 50 081-2,
Measurement complying with EN 55 011,
class A
Limit value 40 dB (µV/m) in 10 m
Limit value 47 dB (µV/m) in 10 m
Limit value 79 dB (µV) with Q
2)
66 dB (µV) with M
Limit value 73 dB (µV) with Q
2)
60 dB (µV) with M
1)
.
Q = measurement complying with
EN 55 011 with quasi peak value
rectifier
2)
M = measurement complying with
EN 55 011 with the mean value rec-
tifier
Requirement from EN 61 131-2,
Measurement complying with
EN 61 131–2
PS2
v10 ms
w24 V
w1 s
Requirements from EN 50 082-2 or EN
61 131-2
Measurement complying with
EN 61 000-4-4
2 kV with DC supplies (direct integration)
2 kV with digital I/Os (capacitive tong-test
instrument)
1 kV serial interface (capacitive tong-test
instrument)
Requirement from EN 61 131-2
Measurement complying with
EN 61 000-4-12
1 kV for DC supplies and digital I/Os
Requirement from EN 50 082-2
Measurement complying with
EN 61 000-4-6
Testing voltage: 10 V
frequency band: 0.15 to 80 Mhz
Modulation: 80 % amplitude modulation
1 KHz
Requirements from EN 50 082-2 or
EN 61 131-2
Measurement complying with
EN 61 000-4-3
7–3
1)
1)