Technical specifications

8.1

Applicability of technical specifications

Note
The following technical specifications only apply under the following conditions:
• The device is in good working order.
• The fan cover and filter pad are installed.
• The device is closed.
• The connected I/O devices meet the requirements for the respective area of application
(interference emission according to EN 61000-6-3 / IEC 61000-6-3, immunity to
interference according to EN 61000-6-2 / IEC 61000-6-2).
8.2

General technical specifications

See the note in "Applicability of technical specifications (Page 145)".
Article number
Dimensions
Weight
Supply voltage (U
)
N
Transient overvoltages
Input current
Operating Instructions, 01/2021, A5E43920357-AA
Device with standard enclosure
6AG4104 -5....-.... (for details, refer to the ordering documentation)
481.4 x 176.6 x 446.6 (W× H × D in mm)
Detailed dimensional specifications can be found in "Dimension drawing of the device
(Page 161)".
15 up to 23 kg; depending on the equipment
Single power supply: 100 V AC to 240 V AC (-15%; +10%)
Redundant power supply:
2 × 100 V AC to 240 V AC (-15%; +10%)
Device is designed for connection to supply with overvoltage category II (transient overvoltages
up to 2500 V)
Single power supply:
Continuous current at 100 V: ≤ 6 A
Continuous current at 230 V: ≤ 3 A
At startup ≤ 80 A for 3.6 ms
Redundant power supply:
Continuous current at 100 V: ≤ 5 A
Continuous current at 230 V: ≤ 2.5 A
At startup ≤ 80 A for 3.6 ms for each module
Information on the dimensioning of fuses in higher-level system circuits
A fuse that is designed for a typical tripping current of 6.3 A is integrated in the power supply
unit of the IPC. The pulse currents during startup are also taken into account by the "time lag"
type. In the case of a fault, this fuse ensures the correct disconnection of the device from the
power supply system.
It is recommended that a fuse of at least 6.3 A, plus the power demand of the other devices that
are also supplied via this circuit, be used for protection of the higher-level power supply circuit.
The tripping characteristic of the higher-level protection must take into account the starting
currents of both the IPC and the other devices.
Device with short enclosure
481.4 x 176.6 x 356.6 (W × H × D in mm)
-
-