MAINTENANCE TIME

Part description
ELECTRODES
FLAME DISC
IONISATION PROBE
COMBUSTION HEAD
COMPONENTS
LIQUID FUEL NOZZLES
INSULATING GASKET
GAS DELIVERY COUPLING SEAL
AIR GRILLE/DAMPERS
AIR DAMPER BEARINGS
FAN
AIR PRESSURE SWITCH
AIR PRESSURE PORT AND
PIPES
FLAME SENSOR
GAS PRESSURE SWITCH
ELECTRIC MOTORS
MECHANICAL CAM
LEVERS/TIE-RODS/BALL JOINTS
ELECTRICAL SYSTEM
INVERTER
CO PROBE
O2 PROBE
HOSES
PUMP FILTER
LINE FILTER
OIL TANK FILTER
GAS FILTER
HYDRAULIC/GAS SEALS
OIL PRE-HEATER
CO CONTROL
CO2 CONTROL
BACHARACH SMOKE INDEX
CONTROL
NOX CONTROL
IONISATION CURRENT
CONTROL
SMOKE TEMPERATURE
CONTROL
DELIVERY/SCAVENGE OIL
PRESSURE CONTROL
GAS PRESSURE REGULATOR
IMPORTANT
In case of heavy-duty operation or when using special fuels, the maintenance intervals must be reduced adapting them to the real
operating conditions, according to the indications of the maintenance technician.
Action to be performed
COMBUSTION HEAD
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK
DISTANCE, CHECK ELECTRICAL CONNECTION
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK
DISTANCE, CHECK ELECTRICAL CONNECTION
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
AIR LINE
GREASING, (Note: apply only on burners with bearings requiring lubrication)
FAN AND SCROLL CLEANING, DRIVE SHAFT GREASING
SAFETY COMPONENTS
FUNCTIONAL INSPECTION
VARIOUS COMPONENTS
COOLING FAN CLEANING, BEARING NOISE CHECK
CHECK OF WEAR AND OPERATION, GREASING OF SLIDING BLOCK AND
CHECK OF ANY WEAR, COMPONENT LUBRICATION
CHECK OF CONNECTIONS AND TERMINAL TIGHTENING
COOLING FAN CLEANING AND TERMINAL TIGHTENING
CLEANING AND CALIBRATION
CLEANING AND CALIBRATION
FUEL LINE
FILTERING ELEMENT CLEANING / REPLACEMENT
CLEANING WITH COLD FUEL OIL
REPLACING THE FILTERING ELEMENT
CHECK OF ANY LEAKAGES
CLEANING, CONDENSATE DRAIN FROM LOWER CAP TO COLD FUEL OIL
COMBUSTION PARAMETERS
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
PRESSURE MEASURED AT START-UP
25 / 36
0006160334_201906
REPLACEMENT
CLEANING
CLEANING
CLEANING
CLEANING
SCREWS
REPLACEMENT
CLEANING
ENGLISH
Gas
Diesel
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
n.a.
YEARLY
YEARLY
n.a.
YEARLY
YEARLY
YEARLY
YEARLY
n.a.
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
n.a.
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
n.a.
5 YEARS
n.a.
YEAR
n.a.
YEAR
n.a.
n.a.
YEAR
n.a.
YEAR
_|C|_
n.a.
n.a.
YEAR
YEAR
YEAR
YEAR
n.a.
YEAR
YEAR
YEAR
YEAR
n.a.
YEAR
YEAR
n.a.
YEAR
YEAR
n.a.

Advertisement