Alarm Status; Notes Regarding 'Request For Alarm Status - Emerson Liebert HiPulse E Series Communications Manual

Modbus / jbus interface
Table of Contents

Advertisement

Communication System Manual
(Modbus/Jbus Interface)
5.7

ALARM STATUS

Address
40030
40031
40032
40033
40034
40035
5.7.1

Notes regarding 'Request for Alarm Status'

Note
Alarms 0 through 15
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit 10
bit 11
bit 12
bit 13
bit 14
bit 15
Note
Alarms 16 through 31
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit 10
bit 11
bit 12
bit 13
bit 14
bit 15
Meaning
Alarm 1- 16
Alarm 17- 32
Alarm 33- 48
Alarm 49- 64
Alarm 65- 80
Alarm 81- 88
Meaning
Not in use
NORMAL OPERATION
BYPASS SWITCH OPEN
OUTPUT SWITCH OPEN
RECTIF. SWITCH OPEN
BATTERY C.B. OPEN
MANUAL BYPASS CLOSED
ECHOMODE
FAN FAILURE ALARM
CRASH LOAD OPTION
BYP: ABSENT
BYP: OVERVOLTAGE
BYP: UNDERVOLTAGE
BYP: FREQUENCY ERROR
BYP: PHASE ROT.ERROR
BYP: SCR FAILURE
Meaning
BYPASS: OFF
BYP: OFF VIA REMOTE
LOAD ON BYPASS
BYP: OVERTEMPERATURE
RECTIFIER: OFF
RECT: OFF VIA DISPL.
RECTIFIER: BLOCK
RECT: CURRENT LIMIT
RECT: OVERTEMPERAT.
RECT: FUSE FAIL
BATTERY FAST CHARGE ON
CAPACITY OVERLOAD PROTECTION
POWER WALKIN ON
LOAD ON INVERTER
INVERTER: OFF
INV: OFF VIA DISPLAY
Range /
Size (bytes)
Resolution
2
2
2
2
2
2
*NOTE
*NOTE
*NOTE
(04/07)
UPS System: HIPULSE E
Description of Protocol
Format
HEX note 1
HEX note 2
HEX note 3
HEX note 4
HEX note 5
HEX note 6
UPS MSS
---
---
---
---
UPS MSS
---
---
---
---
---
---
---
---
---
---
---
---
Page 5-7