Table 2 Scc Control Contacts With Maintenance Bypass; Table 3 Scc Control Contacts To Remote Alarm Status Panel - Emerson Liebert NXL Installation Manual

1600a-5000a, 60hz, three-phase
Table of Contents

Advertisement

Table 2
SCC control contacts with maintenance bypass
Item
Maintenance
Isolation Breaker
(MIB) Form C
Maintenance Bypass
Breaker (MBB) Form C
Maintenance Bypass
Enable Form C
Remote EPO Input
1
Key Status Input Form C
Module Output Breaker
(MIB) Form C
Rectifier Input Breaker
(RIB) Form C
Bypass Input Breaker
(BIB) Form C
1. Key Status Input can be either Form-C, N.O. or N.C. contact
Table 3
SCC control contacts to remote alarm status panel
Terminal
Item
Block
CAN Bus and 24V
TB0829
Power Supply
Terminal
Block
Pin
(Description of External Item)
1
CB aux. contact, closed = CB is closed
TB0811
2
CB aux. contact, common
3
CB aux. contact, closed = CB is open
1
CB aux. contact, closed = CB is closed
TB0813
2
CB aux. contact, common
3
CB aux. contact, closed = CB is open
Maintenance Bypass Cabinet,
1
closed = load not on inverter
TB0821
2
Maintenance Bypass Cabinet, common
Maintenance Bypass Cabinet,
3
closed = load on inverter
1
REPO Switch, normally open contact
TB0825
2
REPO Switch, common contact
1
Key status switch, closed = key removed
TB0820
2
Key status switch, common
3
Key status switch, closed = key inserted
1
CB aux. contact, closed = CB is closed
TB0815
2
CB aux. contact, common
3
CB aux. contact, closed = CB is open
1
CB aux. contact, closed = CB is closed
TB0810
2
CB aux. contact, common
3
CB aux. contact, closed = CB is open
1
CB aux. contact, closed = CB is closed
2
CB aux. contact, common
TB0812
CB or Switch aux. contact,
3
closed = CB or switch is open
Connects to
Pin
(Description of External Item)
1
Remote Status Panel TB-2
2
Remote Status Panel TB-1
3
Remote Status Panel TB-3
4
Remote Status Panel TB-4
7
Control Cable Connections and Communication
Connects to
Wire Size/
Max Length
18AWG/1000ft.
(300m)
®
Liebert
NXL
System Control Cabinet
Wire Size/
Max Length
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)