Rs-485 Electrical Connection With Modbus Network - Emerson Liebert HiPulse E Series Communications Manual

Modbus / jbus interface
Table of Contents

Advertisement

Communication System Manual
(Modbus/Jbus Interface)
3.1.1

RS-485 electrical connection with Modbus network

There is a male 3-way X4 connector for connection with the Modbus network (BMS) on the bottom of the board. To
make the connection, connect a two-wire shielded cable (supplied by others) to the X4 terminal board of the Operator
Logic Board, unless a multipoint connection is required (described in the following paragraph). The female terminal
connector (on X4) is supplied. The wire must have a section of at least 0.25 mm
requirements of ANSI TIA/EIA-485-A standards.
The RS-485 connection cable must finish at each end with a jumper inserted on the Operator board at position X25 1-2;
in the figure below, this must be done on UPS 1 and on the initial connection at the start of the Modbus network.
The following signals are present:
Pin
1
TX+ (RX+) is conventionally the positive wire
2
TX- (RX-) is conventionally the negative wire
3
COM is the ground wire
Use of a two-wire shielded cable with very thick copper braiding in which the shield forms a third constraining wire
(COM) is COMPULSORY.
The impedance of the double wire must be 120 OHMS, in accordance with the RS485 standard.
Page 3-4
Figure 3-4 RS-485 Connection
Description
Table 3-1
(04/07)
UPS System: HIPULSE E
Electrical installation
2
. The cable must comply with the