Quick Start Guide
Note
If hardware or software write protection is not needed, step 10 can
be skipped.
8. Set switches and software write lock.
Note
The write lock switch can be left in the locked or unlocked position.
The simulate enable/disable switch may be in either position for
normal device operation.
8.4
Enable software write lock
Procedure
1. Navigate from the Overview screen.
2. Perform "Write Lock Setup" to enable software write lock.
8.5
AI block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
Parameters
Channel
L-Type
XD_Scale
Note
Select only the units
that are supported
by the device.
Out_Scale
26
a) Check switches (see
a) Select Device Information.
b) Select the Security and Simulation tab.
Enter data
1 = Pressure, 2 = Sensor Temp
Direct, Indirect, or Square Root
Scale and Engineering Units
Pa
bar
kPa
mbar
mPa
psf
hPa
Atm
°C
psi
°F
g/cm
Scale and Engineering Units
Figure
1).
torr at 0 °C
2
kg/cm
2
kg/m
inH
O at 4 °C
2
inH
O at 60 °F
2
2
inH
O at 68 °F
2
March 2020
ftH
O at 4 °C
mH
2
ftH
O at 60 °F
mmHg at 0 °C
2
ftH
O at 68 °F
cmHg at 0 °C
2
mH
O at 4 °C
inHg at 0 °C
2
mmH
O at 68
mHg at 0 °C
2
°C
cmH
O at 4 °C
2
O at 4 °C
2