March 2020
Procedure
1. To verify the device tag:
2. To check the switches (see
3. To disable the software write lock:
Note
Place the control loop in "Manual" mode before beginning analog
input block configuration.
8.3
AI block configuration
Procedure
1. To use guided setup:
Note
For convenience, AI Block 1 is pre-linked to the transmitter primary
variable and should be used for this purpose. AI Block 2 is pre-linked
to the transmitter sensor temperature.
Note
Step 3 through step 6 are all performed in a single step by step
method under guided setup, or on a single screen using manual
setup.
Quick Start Guide
a) Navigation: from the Overview screen, select Device
Information to verify the device tag.
a) Verify the write lock switch is in the unlocked position if the
switch has been enabled in software.
a) Navigation: from the Overview screen, select Device
Information and then select the Security and Simulation tab.
b) Perform "Write Lock Setup" to disable software write lock.
c) Place the control loop in "Manual" mode before beginning
block
configuration.
a) Navigate to Configure → Guided Setup.
b) Select AI Block Unit Setup.
Note
Guided setup will automatically go through each step in the
proper order.
Channel 1 is the primary variable.
Channel 2 is the sensor temperature.
Figure
1):
Quick Start Guide
AI
23