Specifications; Updated Input Update Rate Specification - Allen-Bradley C Series Installation Instructions Manual

Point i/o 8 channel high density current input module
Table of Contents

Advertisement

Indicator Status for Module (Continued)
Status
Off
Flashing green
Green
Network status
Flashing red
Red
Flashing red/green
Off
Flashing green
Channel status
Green
Flashing red
Red

Specifications

IMPORTANT
The input update rate and step response for 1734-IE8C and 1734-IE8CK modules differ from that of catalog numbers 1734-IE2C and 1734-IE2CK
modules.
Input Specifications
Attribute
Number of inputs
Resolution
Input current terminal
(1)
Absolute accuracy
Current terminal
Accuracy drift w/temp.
Current terminal
Input update rate
(per module)
Step response
(per channel)
Input impedance/resistance
Conversion type
Common mode rejection ratio
Description
Device is not online:
— Device has not completed dup_MAC-id test.
— Device not powered – check module status indicator.
Device is online but has no connections in the established state.
Device is online and has connections in the established state.
One or more I/O connections are in timed-out state.
Critical link failure — failed communication device. Device detected error that prevents it from communicating on the
network.
Communication faulted device – the device has detected a network access error and is in communication faulted
state. Device has received and accepted an Identity Communication Faulted Request – long protocol message.
Module in CAL mode.
Channel being calibrated.
Normal (channel scanning inputs).
Channel at end of range (0 mA or 21 mA).
No power or major channel fault.
Value
8, single-ended, non-isolated, current
16 bits — over 0...21 mA
0.32 µA/cnt
4...20 mA
0...20 mA
0.1% Full Scale @ 25 °C
30 ppm/°C
480 ms @ Notch = 50 Hz
400 ms @ Notch = 60 Hz (default)
240 ms @ Notch = 100 Hz
200 ms @ Notch = 120 Hz
120 ms @ Notch = 200 Hz
100 ms @ Notch = 240 Hz
80 ms @ Notch = 300 Hz
60 ms @ Notch = 400 Hz
50 ms @ Notch = 480 Hz
60 ms @ Notch = 50 Hz
50 ms @ Notch = 60 Hz (default)
30 ms @ Notch = 100 Hz
25 ms @ Notch = 120 Hz
15 ms @ Notch = 200 Hz
12.5 ms @ Notch = 240 Hz
10 ms @ Notch = 300 Hz
7.5 ms @ Notch = 400 Hz
6.25 ms @ Notch = 480 Hz
60 Ω
Delta Sigma
-120 dB
Rockwell Automation Publication 1734-IN033E-EN-E - February 2021