Electric Fan Replacement - ViM JBRB ECOWATT PR Instruction Manual

Collective residential building controlled mechanical ventilation
Table of Contents

Advertisement

To access all the unit compartments, unfasten the 4 latches, then remove the unit cover using the handles.
The inlet, discharge and motor compartments are entirely accessible for cleaning.

8.4 Electric fan replacement

8.4.1 JBRB ECOWATT
• Shut off the power supply.
• Unscrew the 2 door screws, then remove the door.
• Disconnect the on-off switch power cable.
• Unfasten the 4 latches, then remove the unit cover using the handles.
• Disconnect the 2 quick connectors behind the control bracket.
• Unscrew the screw inside the control section, then remove the compartment.
• Unscrew the 4 screws on the motor turbine set, then remove the motor turbine set.
JBRB ECOWATT
PR 04 to 22
®
PR 48 to 92
®
44/48
NT00000603-JBRB-ECOWATT-PR-AN-191202