5.

ELECTRICAL CONNECTION

5.1 Prior precautions

Models 30 to 92:
This electronic-switching motor cannot be powered directly by mains power, on pain of destruction. Its
power must be supplied by the controller. The device must be turned on and off via the RMEC local con-
trol (wiring, see §"6.6 Local On/Off control (factory setting)", page 27) or via the BCCA external On/Off
control (wiring, see "5.4 Electrical connection of an external On / Off control", page 17). Do not turn off
the device by directly shutting off the controller's power supply via the INTZ or shutting off the mains power
supply.
Shut off and disconnect the power supply before carrying out any work.
In case of work on the fan, the local on-off switch defined according to IEC947-3/695-2-1 must be open
and locked in this position (according to NF C 15-100).

5.2 Electrical features

Size
JBRB ECOWATT
PR 04
®
JBRB ECOWATT
PR 06
®
JBRB ECOWATT
PR 10
®
JBRB ECOWATT
PR 22
®
JBRB ECOWATT
PR 30
®
JBRB ECOWATT
PR 38
®
JBRB ECOWATT
PR 48
®
JBRB ECOWATT
PR 70
®
JBRB ECOWATT
PR 82
®
JBRB ECOWATT
PR 92
®

5.3 Electrical connection of the local on-off switch

The switch is used to isolate the device from the power supply in case of maintenance, or to turn the device
on/off.
Single-phase 230V
Input power
(kW)
0.07
0.13
0.15
0.35
0.60
0.70
0.72
1.24
1.40
-
JBRB ECOWATT
PR 04 to 22 Single-phase
®
Max. C.
Input power
(A)
0.7
1.0
1.2
1.6
2.6
3.1
3.1
5.4
6.0
-
N L
16/48
NT00000603-JBRB-ECOWATT-PR-AN-191202
Three-phase 400V
Max. C.
(kW)
(A)
-
-
-
-
0.60
1.2
0.70
1.3
0.72
1.5
1.24
2.6
-
1.70
3.5
-
-
-
-
-