6.13 Clock function
Clock mode is used to manage the main operating mode.
This mode is used to select an operating mode and/or specific settings.
Example:
• Main mode is COP at 150Pa
• Clock mode is CAV with:
/h (off) between midnight and 6 a.m., set to 1,000m3/h between noon and 2 p.m. and set
Set to 0m
3
to 500m3/h between 6 p.m. and midnight.
Clock mode
Main mode
0
6
Slot 1
CAV Off
COP 150Pa
• The clock function has 2 standard days (called Cycle 1 and Cycle 2)
• Each cycle has 3 programmable time slots.
• Finally, the different days of the week are allocated to one of the two cycles (e.g.: cycle 1 for week-
days and cycle 2 for weekends)
The Clock function is configured in 5 stages:
• Step 1: by cycle, definition of number of slots
• Step 2: by cycle, definition of type of operation in clock mode
• Step 3: by cycle, definition of time slots
• Step 4: by cycle, setting of set point by slot
• Step 5: allocation of cycles to days of the week
6.13.1 Step 1: by cycle, definition of number of slots
SYSTEM
CONFIGURATION
1 - CONFIGURATION
*
Example given for CYCLE1. At least one time slot must be set in CYCLE1 to be able to programme CY-
CLE2. To modify CYCLE2 replace the P106 steps with the following:
Clock mode
12
Slot 2
CAV 1,000m3/h
2 x
CLOCK
P106 CYCLE1*NUMBER
SLOTS
NUMBER TIMESLOTS
CYCLE1:0
NUMBER TIMESLOTS
CYCLE1:2*
P140 CYCLE2NUMBER
SLOTS
NUMBER TIMESLOTS
CYCLE2:0
NUMBER TIMESLOTS
CYCLE1:2*
Main mode
14
18
COP 150Pa
Cycle 1
3 x
36/48
Clock mode
Main mode
22
Slot 3
CAV 500m3/h
COP 150Pa
Set to the desired number of slots
(max. 3)
*Example
Set to the desired number of slots
(max. 3)
*Example