Group Configurations - Mitsubishi Electric BAC-HD150 Instruction Book

Air-conditioner control system; bm adapter
Hide thumbs Also See for BAC-HD150:
Table of Contents

Advertisement

2.2

Group configurations

®
BACnet
controls each group.
®
BACnet
contol hierarchy consists of M-NET number + Group number + Member number.
Refer to "3.4 Relations between objects and control items" for member number details.
(1) M-NET number
(a) When BAC-HD150 is connected to M-NET
Fixed to 01
(b) When BAC-HD150 is connected to PAC-YG50ECA
M-NET number (01-03)
(2) Group number
Multiple indoor units (IC) can be controlled as a target group. Group number range: 1-50
(3) Member number
Corresponds to Monitor/Operation items of air conditioners
®
BACnet
LAN1
M-NET
BAC-HD150
M-NET number
: 01
M-NET number is fixed to 1.
®
BACnet
HUB
LAN1
BAC-HD150
LAN2
AG-150A
BAC-HD150 is connected to PAC-YG50ECA.
Building Management System
Air Conditioning system
IC
IC
IC
IC
IC
01
02
03
04
05
Group
Group
No.01
No.03
BAC-HD150 is connected to M-NET.
Building Management System
Air Conditioning system
M-NET number
: 01
M-NET
PAC-YG50ECA
00
IC
IC
01
02
Unit address
Group
No.01
M-NET number
: 02
M-NET
PAC-YG50ECA
00
IC
IC
01
02
Unit address
Group
No.01
M-NET number
: 03
M-NET
PAC-YG50ECA
00
Unit address
- 8 -
Unit address
Group number
IC
IC
IC
03
04
05
Group
Unit address
No.03
Group number
IC
IC
IC
03
04
05
Group
Unit address
No.03
Group number

Advertisement

Table of Contents
loading

Table of Contents