Restrictions/Cautions - Mitsubishi Electric BAC-HD150 Instruction Book

Air-conditioner control system; bm adapter
Hide thumbs Also See for BAC-HD150:
Table of Contents

Advertisement

1.2

Restrictions/Cautions

Restrictions and Cautions for BAC-HD150 are as follows.
(1) Restrictions on the system configuration
(a) When BAC-HD150 is connected to M-NET
M-NET
Indoor unit
Symbol
IC
AIC : A-control indoor unit
BU : Air To Water Booster unit
(b) When BAC-HD150 is connected to PAC-YG50ECA (Expansion Controller)
PAC-YG50ECA
AG-150A
BAC-HD150
Indoor unit
• Restrictions on the DB No.
Controllers (PAC-YG50ECA, AG-150A and BAC-HD150) with different DB No. cannot be connected to each other.
When DB No. on the controllers is different, update the software version of the controllers.
Refer to section 3-3 "System in which BAC-HD150 is connected to PAC-YG50ECA (Expansion Controller)" in the
BAC- HD150 Installation Manual for information about DB No.
(2) Connecting AG-150A
• When connecting BAC-HD150 to PAC-YG50ECA, connect AG-150A to set the M-NET address, group, and interlocked
operation with LOSSNAY for PAC-YG50ECA.
(3) Supports for errors
• It is recommended to recover the system immediately when errors related to air conditioning are displayed on the building
management system.
(4) Operation during power failure
• When BAC-HD150 needs to be operated during power failure, a power backup device such as UPS (Uninterruptible Power
Supply) is recommended to be installed.
(5) Functions
• Due to continuing improvement, specifications are subject to change without notice.
(6) Models in a group
• BAC-HD150 monitors and controls indoor units for each group (*1).
To group multiple indoor units, use the same models in a group.
*1 : Group has two types: a unit in a group or multiple units in a group.
(7) Request interval (from BMS* to BAC-HD150) *BMS=Building Management System
• When sending Read_Property or Write_Property from BMS to BAC-HD150, set the interval to 200 (ms/property) or above.
[Ex.1]
Read_Property
Number of connectable units
One line only
50 units max./M-NET
: Indoor unit
Includes the FU (OA processing units)
that are configured in the group but not
interlocked with the indoor units.
Number of connectable units
3 units max.
1 or 2 units
1 unit
150 units max.
(50 units max. / PAC-YG50ECA)
Read_Property
200ms
200ms
Includes all IC, LC, AIC, KIC, BU, AU.
LC : LOSSNAY
KIC : K-control indoor unit
AU : Air To Water HEX unit
Software Version : 1.30 or later
Software Version : 2.30 or later
Software Version : 2.00 or later
Includes all IC, LC, AIC, KIC, BU, AU.
Write_Property
Read_Property
200ms
- 4 -
Notes
Notes
Write_Property
time
200ms