Relations between objects and control items

Object ID consists of object type + instance number.
Instance number consists of M-NET number, air conditioner group number, and member number.
31
®
BACnet
object type
®
BACnet
object type : Refer to the object type as shown in the table below.
Instance number (6 digits in decimal notation) : xx xx xx
Control item
On Off Setup
On Off State
Alarm Signal
Error Code
Operational Mode
Setup
Operational Mode State
Fan Speed Setup
Fan Speed State
Room Temp
[Water Temp]
Set Temp
[Set Water Temp]
Filter Sign
[Circulating Water
Exchange Sign]
Filter Sign Reset
[Circulating Water
Exchange Sign Reset]
Prohibition On Off
Prohibition Mode
Prohibition Filter Sign
Reset
[Prohibition Circulating
Water Exchange Sign
Reset]
Prohibition Set
Temperature
M-NET Communication
State
System
individual
Forced
bundle
Off
Air Direction Setup
Air Direction State
Set Temp Cool
Set Temp Heat
Set Temp Auto
22 21
Inactive
Object
Instance
type
number
Text-1
BO
xxxx01
Stop
BI
xxxx02
Stop
BI
xxxx03
Normal
MI
xxxx04
Normal
MO
xxxx05
Cooling
MI
xxxx06
Cooling
MO
xxxx07
Low
MI
xxxx08
Low
AI
xxxx09
°F/°C
AV
xxxx10
°F/°C
BI
xxxx11
OFF
BV
xxxx12
Reset
BV
xxxx13
Permit
BV
xxxx14
Permit
BV
xxxx15
Permit
BV
xxxx16
Permit
BI
xxxx20
Normal
BV
xxxx21
Reset
BV
999921
MO
xxxx22
Horizontal
MI
xxxx23
Horizontal
AV
xxxx24
°F/°C
AV
xxxx25
°F/°C
AV
xxxx26
°F/°C
Instance number
Member number (01-99)
Group number (01-50, 99)
M-NET number (01-03)
Active
Text-2
Text-3
Run
Run
Error
01: Normal
02: Other errors
03: Refrigeration
system fault
04: Water system error
05: Air system error
Heating
Fan
Heating
Fan
High
Mid 2
High
Mid 2
ON
Void
Prohibit
Prohibit
Prohibit
Prohibit
Error
Execute
Downblow
Downblow
60%
80%
Downblow
Downblow
60%
80%
- 11 -
Text-4
Text-5
06: Electronic
system error
07: Sensor fault
08: Communication
error
09: System error
Auto
Dry
Auto
Dry
Mid 1
Mid 1
Downblow
Swing
100%
Downblow
Swing
100%
0
Notes
Text-6
*1,*2, *5,
Setback
*6, *7, *8
*1,*2, *5,
Setback
*6, *7, *8
*3
*3
*10
*9, *10
*10
*10
*10
*4
*4
*4

Advertisement