Error Display; Recommended Usb Drives - Mitsubishi Electric BAC-HD150 Instruction Book

Air-conditioner control system; bm adapter
Hide thumbs Also See for BAC-HD150:
Table of Contents

Advertisement

(1) Batch operation (Sending the "ON" signal to all groups of units)
Set SW602 to "1110," SW606 to "F," and SW607 to "F," and then press and hold SW605 for two seconds or longer to send the
"ON" signal to all groups of units.
After the "ON" signal has been sent, "End" will appear in the 7segment LED display.
CAUTION:
When executing a batch operation, the "ON" signal will be sent to all groups of units. The
operation status information about each group before the command is executed will not be
stored.
To restore the original operation status before the batch operation command was sent, each
group needs to be set to ON or OFF individually.
(2) Batch operation (Sending the "OFF" signal to all groups of units)
Set SW602 to "1111," SW606 to "F," and SW607 to "F," and then press and hold SW605 for two seconds or longer to send the
"OFF" signal to all groups of units.
After the "OFF" signal has been sent, "End" will appear in the 7segment LED display.
CAUTION:
When executing a batch operation, the "OFF" signal will be sent to all groups of units. The
operation status information about each group before the command is executed will not be
stored.
To restore the original operation status before the batch operation command was sent, each
group needs to be set to ON or OFF individually.
6.8

Error Display

An error code will be displayed in the 7segment LED if an error occurs upon execution of display or operation functions.
No.
Error code
1
Er11
2
Er12
3
Er13
6.9

Recommended USB Drives

The following types of USB drives are recommended for use with BAC-HD150.
• Manufacturer : Sandisk
• Manufacturer : Sandisk
• Manufacturer : Kingston
• Manufacturer : A-DATA
There may be some USB drives that are not compatible with BAC-HD150.
One or more switches on both SW601 and SW602 are set to ON.
One or more of the unavailable switches of SW601 or SW602 are set to ON.
Either SW606 or SW607 is set incorrectly.
Model name : SDCZ6-2048-J65RB
Model name : SDCZ6-4096RB
Model name : DT400/2GBFE
Model name : C702
Cause of error
Memory size : 2GB
Memory size : 4GB
Memory size : 2GB
Memory size : 2GB/4GB
- 29 -