On-Board Web Server; Connect To The Device - Danfoss VLT Soft Starter MCD 600 Installation Manual

Modbus tcp card
Hide thumbs Also See for VLT Soft Starter MCD 600:
Table of Contents

Advertisement

Modbus TCP Card
Installation Guide
Device Configuration
Procedure
1.
Set parameter 1-1 Command Source to Network for the soft starter to accept commands from the Modbus TCP Card.

4.5 On-board Web Server

4.5.1 Connect to the Device

To configure settings using the on-board web server, the Modbus TCP Card must be installed in a soft starter, control power must
be available, and the card and computer must both be connected to the Ethernet network.
The computer must use a fixed IP address (not DHCP) and the same subnet mask as the card. The default IP address for the card is
192.168.0.2. The default subnet mask is 255.255.255.0.
Once connected, the web server reports basic information about the card and the soft starter.
Modbus TCP
Modbus TCP
MCD 600
Danfoss A/S © 2020.12
AN353424224484en-000101 / 130R0946 | 9