Danfoss VLT Soft Starter MCD 600 Installation Manual page 22

Modbus tcp card
Hide thumbs Also See for VLT Soft Starter MCD 600:
Table of Contents

Advertisement

Modbus TCP Card
Installation Guide
Register
Description
40601
Model number
40602
Reserved
40603
Reserved
40604
Starter state
40605
Current
40606
Current
40607
Motor temperature
40608
Power
22 | Danfoss A/S © 2020.12
Bits
Details
15 = MCD 600
0–7
Reserved
8–15
Soft starter model ID
0–4
0 = Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay, restart temperature check, run simulation,
reset input is open)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Uninitialized
1 = Initialized
7
Command source
0 = Remote LCP, Digital Input, Clock
1 = Network
8
Reserved
9
0 = Negative phase sequence
1 = Positive phase sequence
10–15
Reserved
0–13
Average rms current across all 3 phases
14–15
Reserved
0–9
Current (% motor FLC)
10–15
Reserved
0–7
Motor thermal model (%)
8–15
Reserved
0–11
Power
12–13
Power scale
0 = Multiply power by 10 to get W
1 = Multiply power by 100 to get W
2 = Power (kW)
3 = Multiply power by 10 to get kW
Modbus Registers
AN353424224484en-000101 / 130R0946