PROFINET Card
Installation Guide

4.2 Enabling Network Control

If the reset input is active, the soft starter does not operate. If a reset switch is not required, use parameter 7-9 to set the reset
input to normally open or fit a link across terminals RESET, COM+ on the soft starter.
Procedure
1.
Set parameter 1-1 Command Source to Network for the soft starter to accept commands from the PROFINET Card.

4.3 On-board Web Server

4.3.1 Connect to the Device

To configure settings using the on-board web server, the PROFINET Card must be installed in a soft starter, control power must be
available, and the card and computer must both be connected to the Ethernet network.
The computer must use a fixed IP address (not DHCP) and the same subnet mask as the card. The default IP address for the card is
192.168.0.2. The default subnet mask is 255.255.255.0.
Once connected, the web server reports basic information about the card and the soft starter.