Modbus TCP Card
Installation Guide
Register
Description
40609
% Power factor
40610
Voltage
40611
Current
40612
Current
40613
Current
40614
Voltage
40615
Voltage
40616
Voltage
40617
Parameter list version number
40618
Digital input state
40619
Trip code
40620–40631
Reserved
The reset input is normally closed by default. If parameter 7-9 Reset/Enable Logic is set to normally open, the reported state is
inverted (0 = closed, 1 = open).
Danfoss A/S © 2020.12
Bits
Details
14–15
Reserved
0–7
100% = power factor of 1
8–15
Reserved
0–13
Average rms voltage across all 3 phases
14–15
Reserved
0–13
Phase 1 current (rms)
14–15
Reserved
0–13
Phase 2 current (rms)
14–15
Reserved
0–13
Phase 3 current (rms)
14–15
Reserved
0–13
Phase 1 voltage
14–15
Reserved
0–13
Phase 2 voltage
14–15
Reserved
0–13
Phase 3 voltage
14–15
Reserved
0–7
Parameter list minor revision
8–15
Parameter list major version
0–15
For all inputs, 0 = open, 1 = closed (shorted)
0 = Start/Stop
1 = Reserved
2 = Reset
3 = Input A
4 = Input B
5–15 = Reserved
0–7
See the chapter Trip Codes
8–15
Reserved
N O T I C E
Modbus Registers
AN353424224484en-000101 / 130R0946 | 23