Device Configuration

5 Device Configuration

5.1 On-board Web Server

Ethernet attributes can be configured directly in the
EtherNet/IP Module using the on-board web server.
NOTICE
The Error LED flashes whenever the module receives
power but is not connected to a network. The Error LED
5
5
flashes throughout the configuration process.
NOTICE
The default address for a new EtherNet/IP Module is
192.168.0.2. The default subnet mask is 255.255.255.0.
The web server only accepts connections from within the
same subnet domain. Use the Ethernet Device Configu-
ration Tool to temporarily change the network address of
the module to match the network address of the PC
running the tool, if required.
To configure the device using the on-board web server:
1.
Attach the module to a soft starter.
2.
Connect Ethernet port 1 or port 2 on the module
to the network.
3.
Apply control power to the soft starter.
4.
Start a browser on the PC and enter the device
address, followed by /ipconfig. The default
address for a new EtherNet/IP Module is
192.168.0.2.
Illustration 5.1 Entering Network Settings
10
EtherNet/IP Module
5.
6.
7.
NOTICE
If an IP address is changed and its record is lost, use the
Ethernet Device Configuration Tool to scan the network
and identify the module.
NOTICE
If changing the subnet mask, the server is unable to
communicate with the module after the new settings are
saved.

5.2 Ethernet Device Configuration Tool

Download the Ethernet Device Configuration Tool from
www.danfoss.com/drives.
Changes made via the Ethernet Device Configuration Tool
cannot be stored permanently in the EtherNet/IP Module.
To configure attributes permanently in the EtherNet/IP
Module, use the on-board web server.
Configuring the device using the Ethernet Device
Configuration Tool:
1.
2.
3.
4.
Danfoss A/S © 05/2017 All rights reserved.
Edit the settings as required.
Click Submit to save the new settings.
6a
To store the settings permanently in the
module, tick Set permanently.
If prompted, enter username and password.
7a
Username: danfoss
7b
Password: danfoss
Attach the module to a soft starter.
Connect Ethernet port 1 or port 2 on the module
to the Ethernet port of the PC.
Apply control power to the soft starter.
Start the Ethernet Device Configuration Tool.
MG17M202