Modbus TCP Card
Installation Guide
Table 5: Description of Registers in Legacy Mode
Register
Description
40001
Reserved
40002
Command (single write)
40003
Soft starter state
40004
Reserved
40005
Motor current
40006
Motor temperature
40007
Reserved
40008
Reserved
40009–40xxx
Parameter management (sin-
gle or multiple read/ write)
40600
Version
Danfoss A/S © 2020.12
Bits
Details
0–2
To send a command to the starter, write the required value:
1 = Start
2 = Stop
3 = Reset
4 = Quick stop (coast to stop)
5 = Forced communication trip
6 = Start using Parameter Set 1
7 = Start using Parameter Set 2
3–15
Reserved
0–3
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
4
1 = Positive phase sequence (only valid if bit 6 = 1)
5
1 = Current exceeds FLC
6
0 = Uninitialized
1 = Initialized
7–15
Reserved
0–7
Average 3-phase motor current (A)
8–15
Reserved
0–7
Motor thermal model (%)
8–15
Reserved
0–7
Manage soft starter programmable parameters. See the VLT® Soft
Starter MCD 600 Operating Guide for a complete parameter list.
8–15
Reserved
0–5
Binary protocol version
6–8
Parameter list version number
9–15
Product type code:
Modbus Registers
AN353424224484en-000101 / 130R0946 | 21