Modbus TCP Card
Installation Guide
Register
Description
30605
Current
30606
Current
30607
Motor temperature
30608
Power
30609
% Power factor
30610
Voltage
30611
Current
30612
Current
30613
Current
Danfoss A/S © 2020.12
Bits
Details
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Uninitialized
1 = Initialized
7
Command source
0 = Remote LCP, Digital Input, Clock
1 = Network
8
Reserved
9
0 = Negative phase sequence
1 = Positive phase sequence
10–15
Reserved
0–13
Average rms current across all 3 phases
14–15
Reserved
0–9
Current (% motor FLC)
10–15
Reserved
0–7
Motor thermal model (%)
8–15
Reserved
0–11
Power
12–13
Power scale
0 = Multiply power by 10 to get W
1 = Multiply power by 100 to get W
2 = Power (kW)
3 = Multiply power by 10 to get kW
14–15
Reserved
0–7
100% = power factor of 1
8–15
Reserved
0–13
Average rms voltage across all 3 phases
14–15
Reserved
0–13
Phase 1 current (rms)
14–15
Reserved
0–13
Phase 2 current (rms)
14–15
Reserved
0–13
Phase 3 current (rms)
14–15
Reserved
Modbus Registers
AN353424224484en-000101 / 130R0946 | 19