Modbus TCP Module
Installation Guide

5 Device Configuration

5.1 Before Configuring the Device

To avoid IP address conflicts and to ensure successful deployment, connect the device directly to a PC or laptop to configure the
IP address, before connecting to the network.
The error LED flashes whenever the device is receiving power but is not connected to a network. The error LED will flash occa-
sionally during the configuration process.

5.2 Configuration Methods

Ethernet attributes can be configured directly in the device using the on-board web server.
The module is configured with a static IP address as default. A new address can be assigned during configuration, or the device
can be configured to accept a dynamic IP address (via DHCP).
The web server can configure the IP address and messaging settings for MQTT or OPC UA operation.
If it is not possible to connect to the web server, use the Ethernet Device Configuration software to scan the network and identi-
fy the device.

5.3 On-board Web Server

5.3.1 Connect to the Device

To configure settings using the on-board web server, the device must be installed in a soft starter, control power must be available,
and the device and computer must both be connected to the Ethernet network.
The computer must use a fixed IP address (not DHCP) and the same subnet mask as the device. The default IP address for a new
Modbus TCP Module is 192.168.1.2. The default subnet mask is 255.255.255.0.
Once connected, the web server reports basic information about the device and the soft starter.
12 | Danfoss A/S © 2022.11
N O T I C E
N O T I C E
Device Configuration
AN428736661763en-000101 / 175R1189