Installing the Device
2.6 Connecting Power
2.6

Connecting Power

The RUGGEDCOM RST916C features two input terminals that allow the device to be
powered by:
Electrical hazard – risk of power disruption
Due to power supply safety features, some AC voltage will be coupled to the
redundant power terminals (between the positive/live and chassis/ground terminals,
and between the neutral and chassis/ground terminals). While the maximum
amount of current transfer is below the safety threshold, it may be enough to trip
some external Ground Fault Circuit Interrupter (GFCI) breakers. Before connecting
power, review the installation and make sure this condition can be supported.
Note
2.6.1

Connecting AC or DC Power

The device features dual power supply inputs to allow for redundant connections
to separate, independent DC power supplies. Each power supply terminal block
provides reverse polarity protection.
Each variant of the RUGGEDCOM RST916C features dual power supply inputs to
allow for redundant connections to separate, independent external power supplies.
Depending on the device variant, the following are supported:
Each power supply terminal block provides reverse polarity protection.
To connect an external AC or DC power source to the device, do the following:
Note
For examples of the supported wiring configurations, refer to
17)".
14
Up to one independent AC and one independent DC power source
Two independent DC power sources
NOTICE
For 110/230 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker
must be installed.
Use minimum #16 gage copper wiring when connecting terminal blocks.
Equipment must be installed according to applicable local wiring codes and
standards.
One AC power source and one DC power source
Two DC power sources
"Wiring Examples (Page
RUGGEDCOM RST916C
Installation Manual, 04/2021, C79000-G8976-1490-03