60255-27
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RST916C meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RST916C
Installation Manual, 04/2021, C79000-G8976-1490-03
Test
IEC
Dielectric Strength
HV Impulse
Test
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613.1
IEC 61000-4-10
6.2 EMC and Environmental Type Tests
Description
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Description
ESD
Enclosure Contact
Enclosure Air
Radiated RFI
Enclosure Ports
Fast
Signal Ports
Transient
DC Power Ports
AC Power Ports
Earth Ground Ports
Oscillatory
Signal Ports
DC Power Ports
HV Impulse
Signal Ports
DC Power Ports
AC Power Ports
Dielectric
Signal Ports
Strength
DC Power Ports
AC Power Ports
Damped
Enclosure Ports
Oscillating
Magnetic
Field
Test Levels
100% for 0.05 s
2 kV (Failsafe Relay Output)
2 kV or 2.8kV DC
2 kV
5 kV (Failsafe Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV
2.5 kV Common
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
5 kV (Failsafe Relay)
2 kV (Failsafe Relay)
2.8 kVDC or 2 kV
100 A/m for 1 s (100
kHz and 1 MHz)
Certification
Severity
Levels
 
 
 
 
 
 
5 kV
5 kV
2 kV