9 Menu Structure in HMI

Menu
Communication
Ethernet
General
Base Protocol Stack
Internet layer
DHCP client
Host IP address
Subnet mask
Gateway IP address
NTPServer1 IP address
NTPServer2 IP address
Host name
Domain name
DNS1 IP address
DNS2 IP address
Webserver
Access
Reset credentials
Session timeout
EthernetIP
Access
Device status
Vendor ID
Product / Device
Type
Product name
Product code
Product major rev.
Product minor rev.
Settings
EtherNet/IP
Indicates the communication protocol for information purposes only
enabled, disabled
Factory default: enabled. If disabled, the host IP address defaults to 192.168.001.122
Allows for IP address setting 192.168.001.122 is the factory default in case DHCP client is
set to fixed IP
255.255.255.000
factory default: 255.255.255.000
000.000.000.000
Factory default = 000.000.000.000
If it's part of the subnet, the first block of numbers should be identical to HOST IP - for
example, 192.168.1.10
factory default: 000.000.000.000
factory default: 000.000.000.000
factory default: ABB-Flow
factory default: my-domain
automatically set with DHCP = ON: 000.000.000.000
"disabled, Read only,
factory default: Full
Full"
Allows for resetting the webserver password
5 min
Timeout time closing the webserver session.
Default value: 5 minutes
Possible settings: Min: 1 Max: 4294967000
disabled, Read only, Full
Factory Default is disabled
Set to Full or Read Only with Omron or Rockwell PLCs
Mod<G> Net <G> P1
P1 = Port 1 of the Ethernet card
Mod = Module Status
Mod showing <G> continously = Device ready for Operation. Working properly
Mod changing between <G> and < > = Standby. Device not configured yet
Mod changing between <R> and < > = Simple error which can be fixed
Mod showing <R> continously = Major Error. Non removable serious error
Mod showing < > continously = No Power
Net = Network Status
Net showing <G> continously = Connected. Device has at least one established
connection
Net changing between <G> and < > = No Connection. Device did not establish any
connections, but was assigned an IP address
Net showing <R> continously = Dublicated IP address. Device has detected that the
device IP address is already in use
Net showing < > continously = No supply voltage or IP Address.
Net changing between <R> and < > = Connection timeout