12 EtherNet/IP interface details

This section lists all the available classes, attributes and
services included in the EtherNet/IP Interface.
The flow meter supports the following standard objects:
• Identity Object (0x01)
• Message Router Object (0x02)
• Assembly Object (0x04)
• Connection Manager Object (0x06)
• Device Level Ring Object (0x47)
• File (0x37)
• Quality of Service Object (0x48)
• TCP/IP Interface Object (0xF5)
• Ethernet Link Object (0xF6).
Abbreviations for service names:
• GAA = Get Attribute All
• GAS = Get Attribute Single
• SAA = Set Attribute All
• SAS = Set Attribute Single.
[Identity] 0x01
This object provides identification data from and general
information about the device.
Service Code
0x0E
0x01
Table 12 Class-Services
Attr ID
Name
1
Revision
2
Max
Instance
3
Number of
Instances
6
Maximum ID
Number
Class
Attributes
7
Maximum ID
Number
Instance
Attributes
Table 13 Class attributes
Reset-Type
0
Emulated power cycle reset (Power supply off/on, warm
1
The device is reset to factory settings and restarted.
Communication parameters are also reset to factory
2
Return to factory settings except communications
Table 14 Reset
Service Name
Access Rule
Data Type
Get
UINT
Get
UINT
Get
UINT
Get
UINT
Get
UINT
Description
settings, for example, IP address
parameters
Service Code
0x0E
Table 15 Instance-Services
Attr ID
1
2
3
4
0
0
5
6
7
Table 16 Instance attributes
Bit(s)
0-3
4-7
8
The device detected an internal error that can probably be
corrected. The error does not put the device in Error State.
9
GAS
The device detected an internal error that probably cannot
be corrected. Error does not put the device in Error State.
GAA
10
The device detected an internal error that triggered the
11
Value
The device detected an internal error that triggered the
1
12-15
1
Table 17 Description of Bits related for Attribute 5
1
7
ID
0
1
7
2
3
4
5
At least one I/O connection in run mode (not supported)
6
7
At least one I/O connection established, all in idle mode
8
9
start)
10-15
Table 18 Description of Bits 4 to 7 for Attribute 5
Name
Access Rule
Vendor ID
Device Type
Product Code
Revision
Major Revision
Minor Revision
Status
Serial Number
Product Name
Extended Device Status (Refer to Table 18)
Easily recoverable error
Minor unrecoverable error
Serious recoverable error
error status Serious recoverable error in the sensor.
Serious unrecoverable error
error status Serious unrecoverable error in the sensor.
Self-test or unknown (not supported)
Firmware update in progress (not supported)
At least one I/O connection is faulty (not supported)
No I/O connection established
Non-volatile storage is insufficient (not supported)
Serious error (Bit 10 - 11)
Service Name
GAS
Data Type
Get
UINT
Get
UINT
Get
UINT
Get
STRUCT of
Get
USINT
USINT
Get
WORD
Get
UDINT
Get
SHORT_ STRING
Description
Not supported (= 0)
Reserved
Description
0
Reserved
0 (not supported)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hygienicmaster feh630

Table of Contents