WAGO 750-527 Manual page 47

4do 30v ac/dc 2.0a ssr 4-channel digital output; 30 vac/dc, 2.0 a, solid-state for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-527 4DO 30V AC/DC 2.0A SSR
Explosive atmosphere occurring simultaneously with assembly, installation or
repair work must be ruled out. Among other things, these include the following
activities
Insertion and removal of components
Connecting or disconnecting from fieldbus, antenna, D-Sub, ETHERNET or
USB connections, DVI ports, memory cards, configuration and
programming interfaces in general and service interface in particular:
Wiring (connecting or disconnecting) of non-intrinsically safe circuits is only
permitted in the following cases
The circuit is disconnected from the power supply.
The area is known to be non-hazardous.
Outside the device, suitable measures must be taken so that the rated voltage is
not exceeded by more than 40 % due to transient faults (e.g., when powering the
field supply).
Product components intended for intrinsically safe applications may only be
powered by 750-606 or 750-625/000-001 bus supply modules.
Only field devices whose power supply corresponds to overvoltage category I or
II may be connected to these components.
Operating DIP switches, coding switches or potentiometers
Replacing fuses
Use in Hazardous Environments
47
Manual
Version 1.0.0

Advertisement

Table of Contents
loading

Table of Contents