3.10 Wiring Outputs - Honeywell MAXPRO MPIP2000U Series Installation And Setup Manual

Integrated security systems
Table of Contents

Advertisement

Installation and Setup Guide
The default settings in MAXPRO Cloud are suitable for this SAB configuration:
Trigger Output 1 = Exterior Siren; and Trigger Output 2 = Strobe. If you
have wired up the SAB as shown, you do not need to change the settings.

3.10 Wiring Outputs

The control panel offers the following outputs:
Four programmable low-voltage trigger outputs (P on page 34): for arming
l
LEDs, smoke detector power reset, etc.
Wire the AUX1 +12V to the output device, and then use one of the trigger
terminals 1 to 4 to switch to ground. The outputs will switch to ground when
activated.
Max. current is 50 mA for each trigger.
For outputs that require a known state (logical 0/1), you can customise the
outputs to use a pull-up resistor by fitting jumpers on the outputs.
Two relay outputs, 28 VDC, 2.8 A max., resistive loads (N/O on page 34).
l
Wire the relays between the common C terminal and the normal closed NC
or normal open NO terminals.
48
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
800-23044 Rev.  A draft_11