5.4.3

Inputs and Outputs

Inputs:
Input wiring is configurable.
Door Status Monitor (DSM): input for door contact. For access monitoring
l
and burglary alarms. Can be used as an entry/exit zone for burglary
protection. In this case:
When the area is disarmed, the DSM will work as a standard DSM; for
o
example, causing a door forced alarm if the door is opened illegally.
When arming/disarming, the DSM will follow the entry/exit route rules.
o
Request to Exit (RTE): request to exit button.
l
Outputs:
Door Strike/Lock: relay dedicated for the door lock.
l
Selectable 12 VDC feed for the relay NC/NO contact using a jumper. In this
case, the circuit current is limited to 1.5 A. For details, see Relay Jumper on
page 74.
LED R: controls the reader red LED (door blocked, e.g. area is armed)
l
LED Y: controls the reader yellow LED
l
LED G: controls the reader green LED
l
BUZZ: controls the reader buzzer.
l
The buzzer output provides audible notifications for the following events:
Card presented: Short beep for .1 seconds.
l
Valid card (ID) presented: Door unlocked will present one long beep for one
l
second.
Command rejected (request for access or request to arm): three short
l
beeps.
Door Forced or Door Held: continuous tone until door is closed or event is
l
cancelled.
5.4.4

Mounting

You can install the Door Control Module against a wall in its own enclosure, or
you can install up to two Door Control Modules in a cabinet, next to and/or
stacked on top of an MPI Remote Power Supply.
The procedure below is for mounting the device on the wall in its own
enclosure. For installing in a cabinet, see Cabinet Mounting with Control Panel or
Remote Power Supply on page 96.
UL
Make sure to mount the DCM inside the protected area.
70
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
800-23044 Rev.  A draft_11