Emerson Rosemount 702 Reference Manual page 79

Wireless discrete transmitter for plunger arrival
Hide thumbs Also See for Rosemount 702:
Table of Contents

Advertisement

Table 7-1:
Device Status
Database Storage
Warning
Fault State Active
Simulation Active
High Power Active
Reference Manual
Diagnostics
(continued)
State the Problem
The device has failed to
write to the database
memory. Any data
written during this
time may have been
lost
Either the host has not
delivered a discrete
command with in the
fault state time, or the
delivered discrete com-
mand from the host in-
dicates a bad status.
The device is in simula-
tion mode and may not
be reporting actual in-
formation.
The device is operating
in a high power mode.
This is not recommen-
ded for this device.
Diagnostics and troubleshooting
Recommended Ac-
Associated Device
tions
Status Bits
1. Reset the device. 2.
Byte 0; bit 2
If logging dynamic da-
ta is not needed, this
advisory can be safely
ignored. 3. If the con-
dition persists, replace
the transmitter.
1. Verify that the dis-
Byte 1, Bit 0
crete control host is
on line and sending
discrete commands. 2.
Ensure that the dis-
crete control host is
sending commands at
least once within the
fault state time (fault
state time can be ad-
justed to meet the
needs of the applica-
tion). 3. Verify that the
discrete control host is
sending commands
with good status . 4. If
the condition persists,
replace the transmit-
ter.
1. Verify that simula-
Byte 8; bit 0
tion is no longer re-
quired. 2. Disable Sim-
ulation Mode in Serv-
ice Tools. 3. Reset the
device.
1. Disable high power
Byte 2; bit 7 only if de-
mode.
vice_powerMode == 1
73