Configuring Device Communications; 3.3.1 Confirm The Device And Protonode Com Settings Match; 3.3.2 Set Node-Id For Any Device Attached To The Protonode; Figure 4: Com Settings - SMC Networks Lochinvar ProtoNode Startup Manual

Table of Contents

Advertisement

3.3

Configuring Device Communications

3.3.1 Confirm the Device and ProtoNode COM Settings Match

Any connected serial devices MUST have the same baud rate, data bits, stop bits, and
parity settings as the ProtoNode.
Figure 4
specifies the device serial port settings required to communicate with the ProtoNode.
Protocol
Baud Rate
Parity
Data Bits
Stop Bits

Figure 5: Lochinvar Modbus COM Board Showing Serial DIP Switches

3.3.2 Set Node-ID for Any Device Attached to the ProtoNode

Set Node-ID for any device attached to ProtoNode. The Node-ID needs to be uniquely assigned
between 1 and 255.
Document the Node-ID that is assigned. The Node-ID assigned is used for deriving the Device
Instance for BACnet/IP and BACnet MS/TP. (Section 7)
NOTE: The Metasys N2 and Modbus TCP/IP field protocol Node-ID is automatically set to be the
same value as the Node-ID of the device.
Port Setting
Modbus RTU
19200
None
8
1

Figure 4: COM Settings

Page 10 of 56
Lochinvar ProtoNode Start-up Guide
IPW
Other Devices
Modbus RTU
9600
None
8
2