Interfacing Protonode To Devices; Device Connections To Protonode; Lochinvar Low Voltage Modbus Rtu Wiring To The Protonode (Armor, Sync/Armor X2, Knight/Knight Xl, Crest, Copper-Fin Ii And Ftxl); Wiring Field Port To Rs-485 Serial Network - SMC Networks Lochinvar ProtoNode Startup Manual

Table of Contents

Advertisement

4

INTERFACING PROTONODE TO DEVICES

4.1

Device Connections to ProtoNode

The ProtoNode has a 3-pin Phoenix connector for connecting RS-485 devices on the R1 port.
NOTE: Use standard grounding principles for RS-485 GND.
Device Pins
RS-485 +
RS-485 -
RS-485 GND
4.1.1 Lochinvar Low Voltage Modbus RTU Wiring to the ProtoNode (Armor,
SYNC/Armor X2, Knight/Knight XL, Crest, Copper -Fin II and FTXL)
On the Lochinvar's Modbus terminal strip, connect Pin A (RS-485+) to B+ (RS-485+) on the
ProtoNode's R1 port 3-pin Phoenix connector.
On the Lochinvar's Modbus terminal strip, connect Pin B (RS-485-) to A- (RS-485-) on the
ProtoNode's R1 3-pin Phoenix connector.
The Shield Pin on the terminal strip (which is Ground) does not need to be grounded to the
ProtoNode.
4.2

Wiring Field Port to RS-485 Serial Network

Connect the RS-485 network wires to the 3-pin RS-485 connector on the R2 port.
o
Use standard grounding principles for RS-485 GND
See Section
5
for information on connecting to the Ethernet network.
BMS
Wiring
RS-485 +
RS-485 -
-
ProtoNode
Pin
Pin Label
Assignment
TX +
RS-485 +
RX -
RS-485 -
GND
RS-485 GND

Figure 6: RS-485 Connections from Devices to the ProtoNode

ProtoNode
Pin
Pin Label
Assignment
+
RS-485 +
-
RS-485 -
GND
RS-485 GND

Figure 7: Connection from ProtoNode to RS-485 Field Network

Page 11 of 56
Lochinvar ProtoNode Start-up Guide
-
G
(Figure
-
G
7)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lochinvar fpc-n54-1998

Table of Contents