Configuring Device Communications; Input Com Settings On The Device Connected To The Protoair; Set Node-Id For The Device Attached To The Protoair; Bacnet: Calculating The Default Device Instance - SMC Networks ProtoAir FPA-W34 Startup Manual

For interfacing the siemens mag6000
Table of Contents

Advertisement

3.3

Configuring Device Communications

3.3.1 Input COM Settings on the Device Connected to the ProtoAir

The connected serial device MUST have the same baud rate, data bits, stop bits, and parity
settings as the ProtoAir.
specifies the device serial port settings required to communicate with the ProtoAir.
Figure 4
NOTE: The COM parameters are adjustable.

3.3.2 Set Node-ID for the Device Attached to the ProtoAir

Set Node-ID for the device attached to ProtoAir to 1.
Document the Node-ID that is assigned to the device. The Node-ID's assigned are used for
deriving the Device Instance for BACnet/IP. (Section 3.3.3)
NOTE: The Modbus TCP/IP field protocol Node-IDs are automatically set to be the same value as
the Node-ID of the device.

3.3.3 BACnet: Calculating the Default Device Instance

The Device Instance value is automatically generated using the following formula:
BACnet Device Instance = (Device Node-ID) + (Default Node Offset)
NOTE: The default Node Offset is 50,000.
For example, if Device A has a Node-ID of 1 then:
BACnet Device Instance A = (1) + (50000) = 50001
NOTE: The Node-ID is set in Section 3.3.2.
To reach a specific BACnet Device Instance result, refer to Section 7.
3.4

Attaching the Antenna

Wi-Fi Antenna:
Screw in the Wi-Fi antenna to the front of the unit as shown in
Port Setting
Protocol
Baud Rate
Parity
Data Bits
Stop Bits

Figure 4: COM Settings

Page 9 of 43
Siemens ProtoAir Start-up Guide
Devices
Modbus RTU
19200
Even
8
1
Figure
32.

Advertisement

Table of Contents
loading

Table of Contents