CONFIGURE THE PROTONODE

7.1

Select Field Protocol and Set Configuration Parameters

On the Web Configurator page, the first configuration parameter is the Protocol Selector.
Select the field protocol by entering the appropriate number into the Protocol Selector Value. Click
the Submit button. Click the System Restart button to save the updated configuration.
NOTE: Protocol specific parameters are only visible when the associated protocol is selected.
NOTE: If Modbus TCP/IP was selected and is used for the field protocol, skip Section 7.2. Device
profiles are NOT used for Modbus TCP/IP.
Ensure that all parameters are entered for successful operation of the gateway. Find the legal value
options for each parameter under the Parameter Description in parentheses.
NOTE: If multiple devices are connected to the ProtoNode, set the BACnet Virtual Server Nodes
field to "Yes"; otherwise leave the field on the default "No" setting.

Figure 19: Web Configurator Showing Protocol Selector Parameter

Page 20 of 56
Lochinvar ProtoNode Start-up Guide