8.1.1

Standards applicable to the EMC directive

Specification
Test item
EN55011
Radiated noise *1
EN55011
Conducted noise *1
EN61000-4-2
Electrostatic immunity *1
EN61000-4-3
Radiated field AM modu-
lation *1
EN61000-4-4
Fast transient burst noise
*1
EN61131-2 :
2003
EN61000-4-5
Surge immunity *1
EN61000-4-6
Conducted RF immunity
*1
Instantaneous power fail-
ure and voltage dips
immunity
Radiated RF immunity
External power supply
fluctuation immunity
*1 The GOT is an open type device (device installed to another device) and must be installed in a conductive control
panel. The above test items are conducted in the condition where the GOT is installed on the conductive control
panel and combined with the Mitsubishi PLC.
*2 QP: Quasi-peak value, Mean: Average value
*3 The above test items are conducted in the following conditions.
30-230MHz QP
230-1000MHz QP:47dB
Test details
Electromagnetic emissions from the
product are measured.
Electromagnetic emissions from the
product to the power line are mea-
sured.
Immunity test in which static electric-
ity is applied to the cabinet of the
equipment.
Immunity test in which field is irradi-
ated to the product.
Immunity test in which burst noise is
applied to the power line and signal
lines.
Immunity test in which lightening
surge is applied to the product.
Immunity test in which a noise
inducted on the power and signal
lines is applied.
Test for checking normal operations
at instantaneous power failure
Test for checking normal operations
when the power supply unit input
voltage is fluctuated
Test for checking if the unit becomes
faulty with a transient voltage of the
internal and external input sides of
the power supply unit or unit power
supply
:40dB
þV/m (10m in measurement range)
þV/m (10m in measurement range)
8.1 Requirements for conformance to EMC Directive
8.1.1 Standards applicable to the EMC directive
Standard value
30M-230MHz QP:
30dB
V/m(30m measurement range) *2, *3
230M-1000MHz QP:
37dB
V/m(30m measurement range) *2, *3
150k-500kHz QP: 79db,
Mean: 66dB *2
500k-30MHz QP: 73dB,
Mean: 60dB *2
4kV Contact discharge
8kV Aerial discharge
80-1000MHz: 10V/m
1.4-2GHz: 10V/m
80%AM modulation @ 1kHz
Power line: 2kV
Digital I/O (24V or more): 1kV
(Digital I/O (24V or less))
250V
(Analog I/O, signal lines)
250V
DC power type
Power line (between line and ground):
Data communication port: 0.5kV
Power line: 3V
Data communication port: 3V
DC power type
10ms (interval 1s or more)
DC power type
20.4V, 28.8V
DC power type
20.4V, 26.4V
1
2
3
4
0.5kV
5
6
7
8
8 - 2