Boiler Sequencing Technology; Introduction; Installation Notes - Watts AERCO Edge CFR 3000 Operator's And Service Manual

Boiler with edge controller, natural gas modulating boilers
Hide thumbs Also See for AERCO Edge CFR 3000:
Table of Contents

Advertisement

SECTION 7 BOILER SEQUENCING TECHNOLOGY
SECTION 7. BOILER SEQUENCING TECHNOLOGY

7.1 Introduction

The Boiler Sequencing Technology system (BST) is an integrated 16 boiler control system. It is built into
the Edge Controller. It has its own sophisticated PID control system designed to simultaneously control
the light off and modulation of up to 16 boilers while achieving maximum operational efficiency.
BST is designed to ensure that all Boilers in the system operate at maximum efficiency. This is
accomplished by lighting off boilers only when all ignited boilers reach or exceed a defined Valve
Position (Fire Rate). Operating all boilers below the defined Fire Rate "Next on VP" (for Next Turn on
Valve Position) ensures that they are firing at their most efficient Fire Rate. One unit the BST network is
defined as the "Manager" and all other units on the network are defined as "Client" units. The Manager
monitors the system Header Temperature, and monitors all Client unit's status information, efficiently
controlling all units in order to achieve and maintain the required BST Setpoint Temperature.
When there is a demand, the Manager will light off the lead boiler based on the BST Sequencing
selection in the BST Cascade Status screen. As system load increases and the valve position of the
ignited unit(s) reaches the Next on VP (% valve position), the Manager will light off the next available
unit. A simplified block diagram of multiple Boilers connected to a BST is shown in Figure 7-1 below.
NOTE: After boiler load is satisfied, the isolation valve remains open for a programmed interval (default = 2
minutes) before closing. When system load is satisfied, the controller will open the isolation valves for all the
boilers. The BST controls the valves via a 0-20 mA signal.

7.1.1 Installation Notes

A ProtoNode is needed for the LonWorks communications protocol. If your installation includes a
ProtoNode SSD (Client-Client Device), you must adhere to the procedure listed below. Failure to
complete these steps can result in the failure of the BST system.
a) Do NOT install the ProtoNode device at the outset of the installation. If the ProtoNode device is
already installed, you must physically disconnect it from the Modbus network on the I/O board.
Figure 7-1: Simplified BST Block Diagram

Advertisement

Table of Contents
loading

Table of Contents