Analog Output (AO) Setup

Analog outputs can be 0 to 10 V
they can be 0 to 100% duty cycle PWM outputs. They
usually come preprogrammed from the factory. An
analog output is wired to a physical pin, either PWM or 10
bit D/A. The source for an analog output can be mapped
from several places including mapping an analog input to
an output.
Analog Voltage Channels
Channel ID 1 maps to connector pin BS3-9
Channel ID 2 maps to connector pin BS3-10
Analog PWM Channels
Channel ID 3 maps to connector pin BS2-15
Channel ID 4 maps to connector pin BS2-16
Channel ID 5 maps to connector pin BS2-17
Channel ID 6 maps to connector pin BS2-18
Channel ID 7 maps to connector pin BS2-19
Channel ID 8 maps to connector pin BS2-20
Channel ID 9 maps to connector pin BS2-21
The analog output screens display differently depending
on the type of output selected (Analog vs PWM).
shows an example of analog output sourced from
3-63
an analog input.
Select channel ID by clicking on the channel ID
1.
name in the Analog/PWM Output Diagnostics
screen (see
Figure
Owner's Manual for Power Zone Connectivity Server
Time Constant (ms)
No filter
No filter
14
15
16
18
20
23
27
34
48
90
voltage outputs, or
Figure
3-63). The channel ID selects
the analog output pin where channel IDs 1-2 are
analog voltage and 3-9 are PWM pins.
Select the source type (A) as analog or control. A
2.
different pick list will be displayed for each.
Select the function code (B) from the pick list.
3.
Scale the output (C). Numbers are entered in the
4.
units the source is measured in. Enter the value at
which the output should be 10 V
value at which the output should be 0 V
scales the output voltage to the source (in source
units).
Check the "Enable" checkbox (D) to enable the
5.
output.
Click "Apply Changes" (E).
6.
A
B
C
D
E
Figure 3-63. Analog Output (AO) Mapping
shows an example of PWM output
1.
Figure 3-64
sourced from an internal control source. Channel
ID 5 (A) is chosen by the user because it is a PWM
analog output type.
Select the source type (B) as analog or control. A
2.
different pick list will be displayed for each.
Select the function code (C) from the pick list.
3.
The module frequency (D) is fixed, and it depends
4.
on the chosen channel. It is displayed as reference
only. The module frequency dictates the final PWM
frequency.
Select the Frequency prescaler (E) and PWM
5.
counts (F) to set the final PWM frequency by the
indicated
formula. The
Installation and Operation
. Enter the
. This
007571
PWM
counts
value
29

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Power Zone PZCONSVR and is the answer not in the manual?

This manual is also suitable for:

10000039844

Table of Contents