Operation; Local Indicator, Test Points, And Switch; Power Extend Converter High Voltage Shutdown And Lockout; Lockout Restart - Vertiv eSure C48/58-1000B Installation And User Manual

Power extend converter
Hide thumbs Also See for eSure C48/58-1000B:
Table of Contents

Advertisement

OPERATION

Local Indicator, Test Points, and Switch

Location and Identification
Refer to Figure 7.
Indicator
There is one (1) indicator located on the power extend converter's front
panel. Refer to Table 8 for the function of this indicator. Refer also to Table
8 for the alarm contact state for each indicator function.
Test Points
There are two (2) test points located on the power extend converter's front
panel (Vout- and Vout+) for measurement of output voltage.
Switch
There is one (1) switch located on the power extend converter's front panel.
To place the power extend converter into operation, place the switch in the
"enable" position. To remove the power extend converter from operation,
place the switch in the "disable" position.
Power Extend Converter High Voltage Shutdown and
Lockout Restart and Power Extend Converter Overcurrent
Shutdown and Lockout Restart
If the power extend converter experiences a high voltage or overcurrent
condition on the output, the power extend converter shuts down and locks
out. The power extend converter must be manually restarted. Refer to the
following procedure to restart the power extend converter.
Procedure
1.
Turn the power extend converter off and then back on by placing the
front panel enable/disable switch to the disable position and then to
the enable position.