Vertiv 584622100 Installation And User Manual

Netsure +24 vdc to -48 vdc converter system
Hide thumbs Also See for 584622100:
Table of Contents

Advertisement

Quick Links

NetSure™ +24 VDC to -48 VDC
Converter System
Installation and User Manual
Specification Number:
584622100 (19" Main Shelf)
584622200 (19" Expansion Shelf)
584622300 (23" Main Shelf)
584622400 (23" Expansion Shelf)
Model Number: DCS48375

Advertisement

Table of Contents
loading

Summary of Contents for Vertiv 584622100

  • Page 1 NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Specification Number: 584622100 (19” Main Shelf) 584622200 (19” Expansion Shelf) 584622300 (23” Main Shelf) 584622400 (23” Expansion Shelf) Model Number: DCS48375...
  • Page 2 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 3: Table Of Contents

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual TABLE OF CONTENTS Admonishments Used in this Document ..........................v Important Safety Instructions ..............................vi 1 Description and Installation Acceptance Checklist ....................1 1.1 System Description ..................................................1 1.2 Installation Acceptance Checklist ..........................................
  • Page 4 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 8.4 System Troubleshooting Information ........................................28 8.5 Replacement Information ..............................................29 8.6 Replacement Procedures ..............................................29 8.6.1 Replacing a Converter Module .......................................29 8.6.2 Replacing a Distribution Device......................................29 8.6.3 Replacing the System Interface Circuit Card ................................31...
  • Page 5: Admonishments Used In This Document

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA)
  • Page 6: Important Safety Instructions

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page v. Safety and Regulatory Statements Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements.
  • Page 7: Description And Installation Acceptance Checklist

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 1 Description and Installation Acceptance Checklist 1.1 System Description +24 VDC to -48 VDC @ up to 375 A Converter System. The NetSure™ DCS48375 Converter System is comprised of a main shelf and up to two (2) expansion shelves. Each shelf provides mounting positions for up to four (4) converter modules.
  • Page 8: Installation Acceptance Checklist

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 1.2 Installation Acceptance Checklist Provided below is an Installation Acceptance Checklist. This checklist helps ensure proper installation and initial operation of the system. As the procedures presented in this document are completed, check the appropriate box on this list. If the procedure is not required to be performed for your installation site, also check the box in this list to indicate that the procedure was read.
  • Page 9: Installing The System

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2 Installing the System 2.1 General Requirements • The shelf is designed for mounting in a 19-inch or 23-inch wide relay rack with 1-3/4 inch multiple drilling.
  • Page 10: Installing Optional Wiring Access Cover On Top Of Shelf(S), If Desired

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.2 Installing Optional Wiring Access Cover on Top of Shelf(s), If Desired The optional wiring access cover is a 1U high panel that is installed on top of the shelf(s) to allow greater access to load distribution return connection points.
  • Page 11: Mounting The Shelf(S)

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.3 Mounting the Shelf(s) The 584622100 and 584622200 shelves are equipped with reversible mounting angles for mounting in a standard 19 inch or 23 inch wide relay rack having 1-3/4 inch multiple drillings.
  • Page 12: Securing The Expansion Shelf(S) To A Relay Rack And Installing The Expansion Wiring Cover On The Main Shelf

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.4 Securing the Expansion Shelf(s) to a Relay Rack and Installing the Expansion Wiring Cover on the Main Shelf Securing an Expansion Shelf to a Relay Rack Secure an expansion shelf to a relay rack, directly below the shelf above it, per the previous procedure.
  • Page 13: Installing Optional Lug Adapter Busbar Kits

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.5 Installing Optional Lug Adapter Busbar Kits Procedure Refer to Figure 2.4 to install the optional lug adapter busbar kits. Figure 2.4: Installing Optional Lug Adapter Busbar Kits P/N 545404 1.
  • Page 14: Installing Bullet Nose Circuit Breakers And/Or Fuseholders (With Tps/Tpl Fuses)

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.6 Installing Bullet Nose Circuit Breakers and/or Fuseholders (with TPS/TPL Fuses) ALERT! For ambient temperatures at or below +40°C (+104°F), overcurrent devices rated 100A or greater MUST HAVE an empty mounting position between it and any other overcurrent protective device.
  • Page 15 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Figure 2.5: Installing Bullet Nose Circuit Breakers and/or Fuseholders (with TPS/TLS Fuse) 584622100 / 584622200 shown. 584622300 / 584622400 similar. Shorter Side Shorter Side to the Top...
  • Page 16: Installing An Optional Bullet Nose Gmt Fuse Block

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 2.7 Installing an Optional Bullet Nose GMT Fuse Block ALERT! At 40°C ambient, GMT fuses greater than 10A MUST HAVE an empty mounting position between it and any other fuse.
  • Page 17 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Figure 2.6: Installing an Optional Bullet Nose GMT Fuse Block 584622100 / 584622200 shown. 584622300 / 584622400 similar. Press in tabs to release lug terminal busbars for positions to be occupied by GMT Fuse Block.
  • Page 18: Setting Jumper And Switch Options

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 3 Setting Jumper and Switch Options 3.1 Jumper and Switch Settings on the System Interface Circuit Card Perform the following procedures to verify the factory settings and/or make the required settings per your site requirements. These procedures can also be used to make adjustments on a replacement circuit card.
  • Page 19 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Jumper P2 Jumper P2 is the CAN termination jumper. When in stand-alone mode, the jumper P2 must be in place to ensure reliable communications. When an ACU+ is on the CAN bus, jumper P2 should be removed.
  • Page 20: Making Electrical Connections

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4 Making Electrical Connections 4.1 Admonishments Observe the admonishments located at the beginning of this document. 4.2 Wiring Considerations All wiring should follow the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and applicable local codes.
  • Page 21: Shelf(S) Grounding (Frame Ground) Connection

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4.3 Shelf(s) Grounding (Frame Ground) Connection For shelf grounding requirements, refer to the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local codes, and your specific site requirements.
  • Page 22: External Alarm, Reference, Monitoring And Control Connections

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4.4 External Alarm, Reference, Monitoring and Control Connections External alarm, reference, monitoring, and control connections are made to terminals of TB1 and TB2 located on the system interface circuit card mounted on the inside of the main shelf’s front door.
  • Page 23 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Output Current Signal Reference The output current signal (also provided at the output current test points on the front door of the main shelf) can be selected to be referenced to plus battery (input), referenced to minus battery (input), or not referenced as detailed below.
  • Page 24: Load Connections

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4.5 Load Connections To Distribution Bus Row 1/4-20 x 0.625” studs on 5/8” centers are provided for installation of customer provided load distribution leads terminated in 2-hole lugs.
  • Page 25 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual To Optional Bullet Nose 6-Position GMT Fuse Block ALERT! Observe correct polarity when making connections. Otherwise equipment damage may occur. Procedure For load connections to an optional GMT fuse block, refer to Figure 4.4.
  • Page 26: Expansion Shelf(S) Interconnections

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4.6 Expansion Shelf(s) Interconnections Installing Output Paralleling Leads Procedure Perform the procedure in Figure 4.5 for each expansion shelf. Figure 4.5: DC Output Paralleling Interconnections Cable, lugs (P/N 144511), and labels are 1.
  • Page 27 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual FA/CBA and CAN Bus Interconnections Procedure Perform the procedure in Figure 4.6 for each expansion shelf and to connect an external FA/CBA alarm lead to this system.
  • Page 28: Dc Input Connections

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 4.7 DC Input Connections 3/8-16 x 0.875” studs on 1” centers are provided for installation of customer provided DC input leads terminated in 2-hole lugs. Terminations are provided for each converter module (individual feed). Adapter busbars are provided loose with each shelf which allows two (2) converter modules to be fed by a single input.
  • Page 29 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Figure 4.7: DC Input Connections 584622100 / 584622200 shown. 584622300 / 584622400 similar. Rear Rear panels removed in illustration. DC Input Leads Return Enter Here Converter #1 (top)
  • Page 30: Installing The Converter Modules And Initially Starting The System

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 5 Installing the Converter Modules and Initially Starting the System 5.1 Installing Converter Modules The converter module is hot swappable. It can be installed with the system operating.
  • Page 31: Initially Starting And Checking System Operation

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 5.2 Initially Starting and Checking System Operation 5.2.1 Initial Startup Preparation • Ensure that all blocks, except the last one, in the “Installation Acceptance Checklist” starting on page 2 have been checked.
  • Page 32: Operating Procedures

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 6 Operating Procedures 6.1 Converter Modules Refer to UM1C24481500 (Converter Module User Instructions) for converter module operation instructions. 6.2 Using the Converter System with an ACU+ Controller The following outlines the steps to set-up the converter system to be used with an ACU+ controller.
  • Page 33: Test Points

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 6.3.2 Test Points The following test points are provided on the front door of the main shelf. Refer to Figure 6.1. Output Voltage (+, -): Provided for measuring system output voltage.
  • Page 34: Maintenance

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 7 Maintenance 7.1 Admonishments Observe the admonishments located at the beginning of this document. 7.2 System Maintenance Procedures It is recommended to perform and record the maintenance procedures listed in Table 7.1 every 6 months to ensure continual system operation.
  • Page 35: Replacement Information

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 8.5 Replacement Information When a trouble symptom is localized to a faulty converter module, the converter module should be replaced in its entirety. Other than a converter module fan replacement, no attempt should be made to troubleshoot or repair individual components on any converter module.
  • Page 36 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Replacing a TPS/TLS Fuse NOTE! Refer to Figure 2.5 as this procedure is performed. Procedure Open the shelf’s front door. Remove the fuse carrier from the mounted fuseholder body by pulling it straight out.
  • Page 37: Replacing The System Interface Circuit Card

    Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual 8.6.3 Replacing the System Interface Circuit Card ALERT! The system interface circuit card contains static-sensitive devices. Read the Static Warning at the front of this document before performing the following procedure.
  • Page 38 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Figure 8.2: Replacing the System Interface Circuit Card System Interface Circuit Card Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 39 Vertiv™ NetSure™ +24 VDC to -48 VDC Converter System Installation and User Manual Connect with Vertiv on Social Media https://www.facebook.com/vertivI https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/ Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 40 Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.