Initially Starting And Checking Rectifier Operation; Initially Starting The Rectifier; Checking Rectifier Status; Checking Battery Status - Vertiv NetSure IPE Series Installation And User Manual

-48 vdc outdoor rectifier
Hide thumbs Also See for NetSure IPE Series:
Table of Contents

Advertisement

5 Initially Starting and Checking Rectifier Operation

5.1 Initially Starting the Rectifier

Procedure
1.
Verify all customer side DC load output connections are properly terminated, carefully paying attention to +/- DC polarity
at the output. Customer must verify DC polarity output to load before energizing rectifier.
2.
With battery power disconnected by placing the battery ON/OFF switch to the Off position, apply AC input power to the
rectifier by closing the external AC disconnect or protective device. The rectifier starts automatically.
3.
Apply battery power to the system by placing the battery ON/OFF switch to the ON.

5.2 Checking Rectifier Status

Procedure
1.
Observe the status of the local indicators (visible from the outside through a window located on the left side of the
rectifier). If operating normally, the status of these is as shown in Table 5.1. See Figure 6.1 for location.
Table 5.1 Status and Alarm Indicators
Indicator
Status (Green)
Observation Alarm (Yellow)
Critical or Major Alarm (Red)

5.3 Checking Battery Status

The battery connection and charging status can be verified via Bluetooth APP.
Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Normal State
On
Off
Off
Proprietary and Confidential © 2022 Vertiv Group Corp.