OPERATION

Local Indicators

Location and Identification: Refer to Figure 1.
Description: There are three (3) indicators located on the converter module's front panel. The functions of
these indicators are as shown in Table 3.
NOTE!
DC voltage must be present at the converter module input terminals, (from battery or an
operating Rectifier) for local indicators to illuminate.

Converter High Voltage Shutdown and Lockout Restart

Remove the converter, wait 30 seconds or more (until the LEDs on the converter extinguish), then re-insert the
converter.
The converter may also be restarted from the controller. Refer to the controller's
Figure 1:
Local Indicator Locations
Table 3:
DC-DC Converter Module Indicators
Indicator
Power
(Green)
Protection
(Yellow)
Alarm
(Red)
Vertiv
| NetSure DC/DC Converter Module User Manual (UM1C24481500 / 11WA6101WB) | Rev. G
DC-DC CONVERTER MODULE
Normal State
Alarm State
Off
On
Flashing
On
Off
Flashing
On
Off
Flashing
documentation.
Power Indicator
(Green)
Protection Indicator
(Yellow)
Alarm Indicator
(Red)
Alarm Cause
No input voltage.
Internal input fuse open.
The converter is being identified by the
controller.
DC input under/over voltage.
Moderate load sharing imbalance.
Converter not inserted into the slot
completely.
Converter over-temperature protection.
Converter in ECO Standby Mode when ECO
Mode is active in controller.
Loss of communication with the controller
(the converter can provide power).
Severe load sharing imbalance.
Converter output disabled for any reason,
including overvoltage shutdown.
One or both fans not operating (converter
shuts down).