Temp. °F/°C
75 / 24
80 / 27
85 / 29
90 / 35
95 / 35
Table 12
Temperature sensor resistance values - 10K ohms

8.2.2 Fan

Operating power is provided by means of a separate 120 VAC connector (white/black/green). Control
of the fan is provided via a four-lead connector. This connector feeds a PWM control signal (black wire)
from the controller and provides a tachometer signal (white wire) back from the fan. Unplugging the
control connector will cause the fan to go to high speed and trigger a "Blocked Vent Error" within 6
seconds if the boiler is operating.

8.2.3 Air pressure sensor

The air pressure sensor monitors air flow in the venting system. If airflow through the combustion air
intake or the exhaust vent becomes too restricted for safe operation, the boiler will stop firing, and
display a "Fan Pressure Error". Also, to prevent avoidable Fan Pressure Errors, the system decreases
the fan speed if the reading from the sensor nears the error threshold.

8.2.4 Water pressure sensor

The water pressure sensor ensures that there is adequate pressure in the heating system for safe
operation. The pressure is displayed in PSI as the default. If the system pressure should drop below
8PSI the firing rate of the boiler is reduced. If the pressure drops to 4PSI or lower, the boiler will not fire.
Check the operation of the sensor by isolating the boiler from its system piping, and close the system
fill valve, and then crack the pressure relief valve. The pressure displayed should reflect declining
pressure. If it remains "fixed", drain the boiler and replace the sensor, or dislodge any blocking debris
from the sensor inlet channel and reinsert.
Resist.
Temp. °F/°C
Ω – Ohm
10,501
9,299
8,250
7,334
6,532
107
Resist.
Ω – Ohm
175 / 79
180 / 82
185 / 85
190 / 88
195 / 91
8.2.2 Fan
1,281
1,172
1,073
983
903