Testing The Ignition Safety Shutoff; Commissioning; Checking A Boiler's Fuel Source - IBC EX Series Installation & Operating Manual

Commercial condensing boilers
Table of Contents

Advertisement

6.2 Testing the ignition safety shutoff

To test the ignition system safety shutoff device:
1. With the boiler in operation, shut off the gas control valve directly outside the boiler case.
2. Ensure that the boiler has purged, attempted to re-light three times, has shut off and the
appropriate error information is displayed on the controller.
3. The error is displayed after testing the ignition safety shutoff.
4. To restart the boiler, reset the power or on the
's Main Menu, tap Diagnostics>Advanced
controller
Diagnostics>Clear Errors>Yes>OK.

6.3 Commissioning

The EX modulating boilers are factory calibrated to operate with
natural gas (or propane if desired) at sea level. The gas-air ratio or
zero-offset adjustment screw may need adjusting to attain optimum
combustion results. Note that only qualified technicians using
properly functioning and calibrated combustion analyzing equipment
should perform a mixture adjustment.

6.3.1 Checking a boiler's fuel source

This boiler model can burn either natural gas or propane if equipped with the correct fuel-air
metering device. Examine the rating plate of the boiler to ensure it is configured for the fuel you
are using. If the boiler is configured for natural gas, but needs to be converted to propane, use the
conversion kit (sold separately by IBC) to install the appropriate fitting(s) and adjust the gas
valve accordingly. See
The
touchscreen controller
appropriate adjustments to operate the boiler up to 4,500 feet in elevation without de-ration. The
boiler will automatically de-rate at altitudes above 4,500 feet.
Table 10
for the required conversion kit.
will automatically detect the installation's altitude and make the
66
Section: Boiler operation
touchscreen

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ex 400Ex 500Ex 700Ex 850

Table of Contents