Specifications; Operating The Monitor - Badger Meter Blancett B2800 Programming Manual

Flow monitor
Hide thumbs Also See for Blancett B2800:
Table of Contents

Advertisement

Flow Monitor, B2800 Flow Monitor – Simplified

SPECIFICATIONS

Power Supply Options
Battery Powered
Loop Powered
Alphanumeric Rate and Total Display
Accuracy
Temperature Drift
Mounting Classification
Meter Mount
Remote Mount
Swivel Mount
Environmental
Operating Temperature
Humidity
Inputs
Magnetic Pickup Input
Outputs
Type
Maximum Voltage
Pulse Width
Current (ON state)
Optional
Certifications
CSA
UL
CE

OPERATING THE MONITOR

The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode Both the RUN mode and the
PROGRAM mode display screen enunciators confirming the state of the monitor A quick glance at the lower left-hand corner
of the LCD screen will confirm operating status Normal operation will be in the RUN mode To access the PROGRAM mode,
press MENU until the first programming screen is displayed After programming the display with the necessary information, a
lock out feature can be turned on to prevent unauthorized access or changing the meter's setup parameters
Page 6
One D size, 1 5V alkaline battery
Optional 4-20 mA loop power
Eight digit, 0 75 inch high numeric display
Eight character, 0 38 inch high alphanumeric display
Fixed or toggle modes of operation for flow rate and totalizer display
±0 1%
50 ppm / °C (maximum)
Type 4X enclosure
Type 4X enclosure
Type 4X enclosure
–22...158° F (–30...70° C)
0...90% non-condensing
Frequency Range: 0...3500 Hz
Trigger Sensitivity: 30 mV p-p
Over Voltage Protected: ±30V DC
Opto-isolated open collector transistor
30V DC
20 mS/maximum rate 20 Hz
0 9V drop @ 5 0 mA or 0 7V drop @ 0 1 mA
4-20 mA output
Class I, Div 1 Groups C, D; Class II, Div 1 Groups E, F, G
Class I, II, III Div 1 Groups C, D
IEC 61326-1
November 2013