Troubleshooting Guide; Default K Factor Values - Badger Meter Blancett B2800 Programming Manual

Flow monitor
Hide thumbs Also See for Blancett B2800:
Table of Contents

Advertisement

TROUBLESHOOTING GUIDE

Trouble
No LCD Display
No Rate or Total
Displayed
Flow Rate Display
Interprets Reading
Constantly
Flow Rate Indicator
Bounces

DEFAULT K FACTOR VALUES

Meter Size
0 375
0 500
0 750
0 875
1 000
1 500
2 000
3 000
4 000
6 000
8 000
10 000
November 2013
• Check battery voltage Should be 1 5V DC Replace if low or bad
• Check connection from meter pickup to display input terminals
• Check turbine meter rotor for debris Rotor should spin freely
• Check programming of flow monitor
• This is usually an indication of external noise Keep all AC wires separate from DC wires
• Check for large motors close to the meter pickup
• Check for radio antenna in close proximity
• Try disconnecting the pickup from the monitor pig tail This should stop the noise
• This usually indicates a weak signal Replace pickup and/or check all connections
• Examine K factor
Default K factor
20,000
13,000
2750
2686
870 0
330 0
52 0
57 0
29 0
7 0
3 0
1 6
Remedy
Lower Limit
16,000
10,400
2200
2148
696 0
264 0
41 6
45 6
23 2
5 6
2 4
1 3
Programming Manual
Upper Limit
24,000
15,600
3300
3223
1044
396 0
62 0
68 0
35 0
8 0
4 0
2 0
Page 11