The limit as set by the user in the CCGX will be applied to all inputs where 'Overruled by remote',
configured with VEConfigure, is enabled:
Using the example of a boat with two AC inputs and a Quattro where:
1.
A Genset capable of delivering 50A is connected to input 1;
2.
Shore power is connected to input 2. (Available power depends on the rating of the harbour
power-supply.)
Configure the system exactly as in above VEConfigure screenshot. Input 1 has priority over input 2,
therefore the system will automatically connect to the genset whenever it is running. The fixed input
current limit of 50A will be applied. And when the genset is not available, and mains is available on
input 2, the Quattro will use the input current limit as configured in the CCGX.
Two more examples: (In both cases if you disable 'Overrule by remote', setting a current limit in the
CCGX will have no effect. And if you enable 'Overrule by remote' for both inputs, the current limit set
in the CCGX will be applied to both inputs.)
Minimum input current limit values
When PowerAssist is enabled in VEConfigure, there is a minimum input current limit. The actual limit
differs for each model.
After setting the input current to a value below the limit, it will automatically be increased again to
the limit.
Note that is still possible to set the input current limit to 0. When set to 0, the system will be in
passthrough (charger disabled).